IPP-07ea-330-1 “Gelios - 3 IR” RS Multirange Explosion-Proof Flame Fire Detector
The detector is designed for detection of ignition of various substances based on electromagnetic radiation of flame in the UV band and for sending of alarm signals to the fire alarm loop.
The multirange explosion-proof flame detector is designed for sending an alarm signal to the fire alarm and control panels in case of detection of ignition of materials followed by open flame within the viewing field of the detector. It is used at chemical, oil and gas production, oil and gas processing industry enterprises and in explosion hazardous areas of other production facilities.
ATTENTION! All detectors manufactured by Eridan JSC meet the requirements of effective regulations, rules, norms and other reference documentation. Pursuant to mandatory requirements of GOST R 53325-2012*, after activation and alarm initialization, all current-consuming fire detectors (IP) must switch to standby mode ONLY after being de-energized or if so commanded by the FACP.
Distinctive features:
Design:
Key features:
You can as well purchase our fire detectors IPP-07ea “Gelios-IR/UF" RS, IPP-07e “Gelios - 2 IR" and others.
To order a fire detector, please call: +7 (343) 351-05-07 or use our Quotation generation tool
Our e-mail: market@eridan-zao.ru
explosion proofness marking
|
1Exd IICT6Gb Х
|
supply voltage, V
|
8-28
|
detector current consumption, max., mA
|
in standby mode: 20
|
in activation mode: 30 | |
in all modes during polling: 50 | |
when heating is on: 200 | |
operating conditions, °С
|
with heating: от -60 до +55
|
without heating: от -40 до +55 | |
ingress protection rating | IP66 и IP67 |
detector viewing angle, min., ° | 90° |
range of detection of TP-5 and TP-6 test sources, min., m | 25 |
Response time, max., sec.
|
10
|
overall dimensions (with canopy, without bracket and cable glands), max., mm
|
146х105х110
|
weight, max., kg
|
1,6
|
lifetime, min., years
|
10 |
warranty period, years
|
5
|
Alteration of the distance, at which a stable actuation caused by the effect of radiation is guaranteed, in case of change of the visual axis direction in spatial angle α in relation to the direction towards the radiation source | |||
0° | ±15° |
±30°
|
±45° |
100% | 96% |
86%
|
71% |
Cable glands designation:
Appearance | Designation | Definition |
ShT1/2" | pipe union for pipe arrangement with the thread G½" | |
![]() |
ShT3/4" | pipe union for pipe arrangement with the thread G¾" |
![]() |
ShT1" | pipe union for pipe arrangement with the thread G1" (NEW!) |
![]() |
Sh M20 | pipe union for pipe arrangement with the thread М20х1.5 (NEW!) |
![]() |
ShT25 | pipe union for pipe arrangement with the thread М25х1.5 (NEW!) |
![]() |
KVB12 | cable gland for armored cable with max.armor Ø 12 mm |
![]() |
KVB17 | cable gland for armored cable with max.armor Ø 17 mm |
![]() |
KVBU14 | cable gland for armored cable with outer diameter 10-14 mm with double seal along the cable external insulation and cable wrapping with any armor type (NEW!) |
![]() |
KVBU18 | cable gland for armored cable with outer diameter 14-18 mm with double seal along the cable external insulation and cable wrapping with any armor type (NEW!) |
![]() |
KVBU22 | cable gland for armored cable with outer diameter 18-22 mm with double seal along the cable external insulation and cable wrapping with any armor type (NEW!) |
![]() |
KVM15 |
cable gland for installation in metal hose with nominal inside diameter Dn=15 mm
|
![]() |
KVM20 |
cable gland for installation in metal hose with nominal inside diameter Dn=20 mm
|
![]() |
KVM25 | cable gland for installation in metal hose with nominal inside diameter Dn=25 mm |
![]() |
KVO10 | cable gland for surface laying of cable with outer diameter of up to 10 mm (NEW!) |
![]() |
KVO14 | cable gland for surface laying of cable with outer diameter of up to 14 mm (NEW!) |
![]() |
ZG |
terminal plug
|
![]() |
OE** | terminal element (OE)* |
*Terminal element (OE) is not a separate device; it is part of one of the option packages for explosion-proof fire detectors IP103-2/1-TR, IP101-07e and series IP101-07 and it is designed for continuous control of fire alarm loop integrity (it is installed in the last annunciator of the loop).
**as per item 13.15.20 of SP 5.13130.2009:
In case there is no visual control of availability of power supply on the fire detectors connected to the fire alarm radial loop, it is recommended to install a device at the end of the loop that will provide visual control of its condition (for example, a blinking signal device)
A LED on the terminal element indicates that the loop is operational. It operates in flashing mode.
OE electrical specifications:
IPP-07ea “Gelios - 3 IR” RS