Call time weekdays 8:00-17:00 Ekaterinburg time 07:07 |
Production | The Company | Installation and configuration | Price | Contact us | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
EXPLOSION-PROOF EQUIPMENT
Analog-addressable system “Dialog-Ex”
Non explosion-proof DEVICES
|
is used for activation of auxiliary mechanisms of fire extinguishing, smoke removal systems, etc.
UDP activation is carried by means of two actions (mandatory requirement to UDP as per current GOST 53325-2012).
It can be connected directly to the control device circuits (modification I1) or to the fire alarm loop in order to interact with the fire alarm control panel (modification I2).
The remote start device is used at chemical, oil and gas production, oil and gas processing, ship-building industry enterprises and in explosion hazardous areas of other production facilities.
Distinctive features of UDP IP535-07e START:
Operational Principle:
Activation of the device is caried out by means of shifting downwards the protective element (1) and pulling out the driving element (2). This cause breaking of the removable element (3). When the driving element (2) is returned into its initial position, the device starts operating in standby mode again (only for modification I1). In order to set the protective element (1) into its working position a new removable element (3) from the supply package will be required. This allows repeated use of the device.
ATTENTION! This operational principle is to be patented (patent application to Rospatent dd. 27.07.2015).
Design:
Key features:
You can as well purchase our fire detectors IP103-2/1-TR, IP101-07md and others.
To order a fire detector, please call +7 (343) 351-05-07
Our e-mail: market@eridan-zao.ru
![]() |
UDP IP535-07e „START“ detector is entered into Stock item identification guide MTR “Gazprom” OJSC. MTR codes of Gazprom (2016) for the CJSC products |
Characteristics of UDP IP535-07e START, modification I1:
UDP IP535-07e START I1 provides closing of control devices circuit when activated.
explosion proofness marking | 1ExdmIICT6 |
dust and moisture resistance | IP66 / IР67 |
maximum allowable switching power, max., W | 10 |
maximum switching voltage, V | 60 |
maximum allowable switching current, A | 0.5 |
indication of operation modes, standby mode / activation mode | yes / no |
operating conditions, °С | from -60 to +85 |
max. overall dimensions, mm | 245x135x80 |
max. weight, kg | 1.0 |
lifetime, min, years | 10 |
warranty period, years | 5 |
Characteristics of UDP IP535-07e START, modification I2:
UDP IP535-07e START I2 can be connected to the fire-safety system loop to activate by circuit opening (series connection) or closing (parallel connection).
explosion proofness marking | 1ЕхdmIICT6 |
dust and moisture resistance | IP66 / IР67 |
supply voltage, V | 8-28 |
maximum current consumption, μA | 70 |
indication of operation modes, standby mode / activation mode | yes / yes |
operating conditions, °С | from -60 to +85 |
max. overall dimensions, mm | 245x135x80 |
max. weight, kg | 1.0 |
lifetime, min, years | 10 |
warranty period, years | 5 |
TU 4371–006–43082497–04
NEW! Canopy for IP535-07e/ea call point and for 535-07е ‘START’ UDP
The canopy is an integral part made of powder-coated steel, it is designed as a means of protection against atmospheric precipitations for explosion-proof call points of IP535-07e series and IP535-07e START remote start device manufactured by Eridan, CJSC.
Appearance | Designation | Definition |
![]() |
Canopy |
If necessary, please, indicate "with canopy" in your order; the canopy is not included in the package by default |
Cable glands designation:
Appearance | Designation | Definition |
ShT1/2" | pipe union for pipe arrangement with the thread G½" | |
![]() |
ShT3/4" | pipe union for pipe arrangement with the thread G¾" |
![]() |
ShT1" | pipe union for pipe arrangement with the thread G1" (NEW!) |
![]() |
Sh M20 | pipe union for pipe arrangement with the thread М20х1.5 (NEW!) |
![]() |
ShT25 | pipe union for pipe arrangement with the thread М25х1.5 (NEW!) |
![]() |
KVB12 | cable gland for armored cable with max.armor Ø 12 mm |
![]() |
KVB17 | cable gland for armored cable with max.armor Ø 17 mm |
![]() |
KVBU14 | cable gland for armored cable with outer diameter 10-14 mm with double seal along the cable external insulation and cable wrapping with any armor type (NEW!) |
![]() |
KVBU18 | cable gland for armored cable with outer diameter 14-18 mm with double seal along the cable external insulation and cable wrapping with any armor type (NEW!) |
![]() |
KVBU22 | cable gland for armored cable with outer diameter 18-22 mm with double seal along the cable external insulation and cable wrapping with any armor type (NEW!) |
![]() |
KVM15 |
cable gland for installation in metal hose with nominal inside diameter Dn=15 mm
|
![]() |
KVM20 |
cable gland for installation in metal hose with nominal inside diameter Dn=20 mm
|
![]() |
KVM25 | cable gland for installation in metal hose with nominal inside diameter Dn=25 mm |
![]() |
KVO10 | cable gland for surface laying of cable with outer diameter of up to 10 mm (NEW!) |
![]() |
KVO14 | cable gland for surface laying of cable with outer diameter of up to 14 mm (NEW!) |
![]() |
ZG |
terminal plug
|
![]() |
OE** | terminal element (OE)* |
*Terminal element (OE) is not a separate device; it is part of one of the option packages for explosion-proof fire detectors IP103-2/1-TR, IP101-07e and series IP101-07 and it is designed for continuous control of fire alarm loop integrity (it is installed in the last annunciator of the loop).
**as per item 13.15.20 of SP 5.13130.2009:
In case there is no visual control of availability of power supply on the fire detectors connected to the fire alarm radial loop, it is recommended to install a device at the end of the loop that will provide visual control of its condition (for example, a blinking signal device)
A LED on the terminal element indicates that the loop is operational. It operates in flashing mode.
OE electrical specifications:
UDP IP535-07e „START“
Введите Email | |
РФ | |
Geography of supplies explosion-proof equipment: Moscow, St. Petersburg, Yekaterinburg, Kazan, Perm, Tyumen, Ufa, etc. | ||||
![]() |
|